![]() |
![]() |



This solar sensor drives the misting as shown to the right. Note the automatic adjustment of the mist interval with change in weather/sunlight. Solar Counts come most quickly in the middle of a sunny day and more slowly on cloudy days or at the ends of day. We call this Variable Solar Misting.
The benefits of Variable Solar Misting are reduced disease, quicker rooting, less runoff, less labor used in adjusting timers and less chemical leaching.
Switching a zone between misting and irrigation is easy. This feature reduces labor in moving pots to different benches as plants mature. This MIST/IRRIGATE decision is chosen for each zone. In the picture below, you can see that Zone 3 is put in MIST mode while Zone5 is put in the IRRIGATE mode. The Irrigation Mode is discussedonthe right.
You can also see that Zone3 is set to mist DAY & NIGHT. Z3 will mist 8+2 seconds x10 equals 100 seconds. The REPEAT interval for Zone3 is set to repeat every 16+8 Solar Units. Nighttime misting is discussed below.
If you have water pressure problems, call us. We have solutions.
Irrigation Mode.......
To get a valve to irrigate, push-on the
MIST/Irr switch as shown for Z5 in the
photo to the left. Then push-on switches
for the desired hours (7am, 1pm and 4pm
irrigation hours chosen below).
The duration of irrigation is the sum of
the counts in both the SECS and REPEAT
switches. So Z5 will irrigation 4 minutes
and 20 seconds. Note the X10 switch is
ignored in the Z5 in the Irrigation Mode.
Only the counts are used for irrigation, not
the multipliers.
Misting has priority over irrigation. So
in the middle of irrigating Z5 at 1pm, Z5
may be stopped to mist some valves. Z5 will
get all the water requested, but all irrigation
may not occur continuously.
The mini-Solar controllers have all the
benefits of the i-series. Limitations are that
all mist valves have the same SEC-ON and
REPEAT INTERVAL and there is no Irrigation
mode. The 8-valve controller sequences through
the valves with a 6-sec delay between each valve.
Nighttime Repeat
can be set at 1, 2, 4
hours and the sum of
these hours.
The Solar 3B mist controller has all the
benefits of the i-series. All mist valves allow
individual setting of SEC-ON and REPEAT
INTERVAL. The controller mists only one
valve at a time with a 6-sec delay between each
valve.
Nighttime Repeat can be set at 1/4, 1/2, 1,
2, 4 and 8 hours and the sum of these hours.
A thermostat input
makes this controller very
good for fog systems. When
the thermostat contact closes,
the Repeat Interval can be
shortened by 5%, 10%, 20%
and the sum of these.
The DE8PR2 mist controller is time-based,
not solar-based. The DE8PR2 uses HOT/
COOL hour definition to give adjustment of
Repeat Intervals as shown below.
All mist valves allow individual setting of
SEC-ON and REPEAT INTERVAL. Only one
valve will run at a time.
Nighttime misting can be set every hour.
The Tstat24 controls 2 stages of heating, 4 stages of cooling and Circulation (HAF).
The HAF can be set to run until either the C1 or C2 stage is reached. The Delay-Between-
Stages is set at 15 seconds but may be increased from 1 to 7 minutes.
The DIFtrol23 and DIFtrol24 easily impliment
the DIF temperature profile pioneed at Michigan State
Univeristy and shown to the right. Three Temperature
References are set by the grower. The Solar Sensor
detects the graying of the eastern sky each morning
and synchronizes the DIFtrollers to advance through
the three Temperature References. The heating and
cooling stages adjust around each Temperature
Reference as described in the Tstat24 write-up.
The 2 air inlet and air outlet ducts are fabricated from the flue vents used to exhaust gas heaters.
The 2 vents in the drawing to the right are shown pointing down. This downward direction traps the
warm air inside the greenhouse until the 12� fan is activated. The position of the vents at the top of
the greenhouse assures that the air with the most moisture is exhausted.
A Honeywell dehumidification controller # H46E1013 (or similar device) can be set at 20% to 80%Rh and placed high near the exhaust
fan to cycle the 12� fan On-Off to maintain healthy conditions. This slow, steady method of reducing humidity is much better than using large
fans and side vents which dump large amounts of very cold winter air onto plants. Also, since these ducts are open, ice-buildup on louvres will
never be an obstacle to dehumidification. Since they are high, the cold air mixes slowly from the small 12" inlet flue vent.
Revised 1-11





Temperature Controllers: Multi-stage thermostats with DIF

The precision of the Tstat 24 will eliminate the first stage of heating and the first stage
of cooling running at the same time which is a common wasteful problem with separate
mechanical thermostats.
The Temperature Reference is set. Then temperature steps are set between this
Reference and each heating and cooling stage. These temperature steps are illustrated by the
white boxes on the face of the Tstat24. You may write your settings inside these white boxes.
DIFtol23 controls 2 stages of heating, 3 stages of
cooling and Circulation (HAF). The Delay-Between-
Stages is set a 15 seconds but may be increased from
1 to 7 minutes.
DIFtol24A controls 2 stages of heating, 4 stages of
cooling and Circulation (HAF). The Delay-Between-
Stages is set at 15 seconds but may be increased from
1 to 7 minutes.
The DIFtrol24A has its entire operating insructions printed on the faceplate.
The precision of the DIFtrollers will eliminate the first stage of heating and first stage
of cooling running at the same time which is a common problem with separate mechanical
thermostats.
The Relay Box-120VAC has a cable that
connects to the Tstat24 or DIFtrollers. The
relays in this controller have 1P2T contacts
rated at 30 amps.
Both heating stages can control 2 heaters.
Up to 4 heaters may be controlled.
The Relay Box-240VAC has a cable that
connects to the Tstat24 or DIFtrollers. The
relays in this controller have 2P1T contacts
rated at 30 amps.
Both heating stages can control 2 heaters.
Up to 4 heaters may be controlled.
Humidity control is a problem in many greenhouses, especially in the snow belt in winter and
fall. Rather than using the large exhaust fans designed for summer cooling to de-humidify, this simple
method uses a small 12� fan and 2 simple exhaust vents which will never ice-close.
or if you prefer you can contact us direct by email
Se Habla Espanol!
© Arthur Enterprises